534372_TF 100Tr_Th-Pk_v02.jpg
Protects measuring transformers; lightning and surge voltage protector for 1A respectively 5A cores in current transformers.
  • Remote signaling contact: closer
  • Protects measuring transformers
  • Very high impulse and AC current resistivity
  • No blow-out vents, thus, not requiring any safety clearance to other installations
  • High insulation resistance Risol: ? 10 G?
  • Very long service life
  • Lightning impulse current discharge capacity 100 kA (10/350 µs)
  • EAC certification
DC spark-over voltage (100V/s)Uag 2000 (-10%/+20%) V=
AC spark-over voltage(100V/s) (50/60Hz)Uaw 1414 (-10%/+20%) V~
Impulse sparkover voltage typ. at 1 kV/µsUas < 3.000 V=
CapacitanceC ≤ 16 pF
Insulation resistance at 10 VRis ≥ 1 GΩ
Nominal discharge current (8/20 µs)In 10 x 60 kA
Lightning impulse current (10/350 µs) (Iimp) + long-time current 200 A/0.5 s/100 AsIpeak / Q / W/R 1x 60 kA / 30 As / 900 kJ/Ω
Lightning impulse current Iimp (10/45 µs) + half-wave 1.6 kA (DIN 48810)Ipeak / Q / W/R 20x 60 kA / 10 As / 100 kJ/ Ω
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100 A/s
Operating temperature rangeTU -40 - +75 °C
Additional Information
Recommended conductor cross section 25 mm²
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Max. connection torque for terminals 4,0 Nm
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on 35 mm DIN rail (EN 60715)
Switching capacity Pk 230 V/1,6 A
Max. conductor cross section Pk 1,5 mm²