534372_TF 100Tr_Th-Pk_v02.jpg
Protects measuring transformers; lightning and surge voltage protector for 1A respectively 5A cores in current transformers.
  • Remote signaling contact: closer
  • Protects measuring transformers
  • Very high impulse and AC current resistivity
  • No blow-out vents, thus, not requiring any safety clearance to other installations
  • High insulation resistance Risol: ? 10 G?
  • Very long service life
  • Lightning impulse current discharge capacity 100 kA (10/350 µs)
  • EAC certification
DC spark-over voltage (100V/s)Uag 500 ±20% V=
AC spark-over voltage(100V/s) (50/60Hz)Uaw 350 ±20% V~
Impulse sparkover voltage typ. at 1 kV/µsUas typ. 1000 / max. 1300 V=
Impulse sparkover voltage at 1 kV/ns (100 MHz)Uas typ. 2800 / max. 3000 V
CapacitanceC ≤ 16 pF
Insulation resistance at 10 VRis ≥ 1 GΩ
Nominal discharge current (8/20 µs)In 10x 100 kA
Lightning impulse current (10/350 µs) (Iimp) + long-time current 200 A/0.5 s/100 AsIpeak / Q / W/R 1x 100 kA / 50 As / 2500 kJ/Ω
Lightning impulse current Iimp (10/45 µs) + half-wave 1.6 kA (DIN 48810)Ipeak / Q / W/R 20x 60 kA /10 As /100 kJ/Ω
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100 A/s
Additional Information
Operating temperature rangeTU -40 - +75 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on 35 mm DIN rail (EN 60715)

Related Products