382079_EP CV 2P 65V_63A_FM_v02.jpg
These devices are predominantly used for cathodic corrosion protection sys-tems at gas and oil pipelines with bitumen insulation layer. For protection of 30 V DC / 36 V AC lines in CCPS up to max. fuse 63 A.
  • Arresters for Cathodic Corrosion Protection Systems
  • Mounting directly on DIN rail
  • Operating current up to 63 A
  • Leakage current-free
IEC category Type 2 /class II
Nominal voltage DCUN 36 V=
Nominal voltage ACUN 30 V~
Max. continuous operating voltage DCUc 65 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 45 V~
Max. acceptable fuse or back-up fuse 63 A gG
Voltage protection level (1 kV/μs)Up ≤ 0,55 kV
Protection level at 1 kV/µs (1, 2-PE)Up ≤ 0,55 kV
Response timetA ≤ 50 ns
Nominal discharge current (8/20 µs)In 20 kA
Additional Information
Max. impulse discharge current (8/20 µs)Imax 40 kA
Lightning impulse current (10/350 µs) per poleIimp 5 (2,5 As) kA
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
Max. conductor cross section FM 1,5 mm²
Max. switching capacity of remote signal contact 250 / 2 V/A

Related Products