382087_EP C 2P_100V_63A_FM_LED_v02.jpg
These devices are predominantly used for cathodic corrosion protection sys-tems at gas and oil pipelines with bitumen insulation layer.
  • Version with and without LED available
  • Arresters for Cathodic Corrosion Protection Systems
  • Mounting directly on DIN rail
  • Operating current up to 63 A
  • Leakage current-free
IEC category Type 2 /class II
Nominal voltage DCUN 100 V=
Nominal voltage ACUN 75 V~
Max. continuous operating voltage DCUc 125 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 95 V~
Max. acceptable fuse or back-up fuse 63 A gG
Voltage protection level (1 kV/μs)Up ≤ 0,6 kV
Response timetA 50 ns
Nominal discharge current (8/20 µs)In 20 kA
Max. impulse discharge current (8/20 µs)Imax 25 kA
Additional Information
Lightning impulse current (10/350 µs) per poleIimp 5 kA
Operating temperature rangeTU -40 - + 80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Max. switching capacity of remote signal contact 250 V / 0,5 A V/A
Max. conductor cross section FM 1,5 mm²
Mounting on 35 mm DIN rail (EN 60715)