EP CV 2P 65V/63A/FM
Article Nr. : 382079
These devices are predominantly used for cathodic corrosion protection sys-tems at gas and oil pipelines with bitumen insulation layer. For protection of 30 V DC / 36 V AC lines in CCPS up to max. fuse 63 A.
- Arresters for Cathodic Corrosion Protection Systems
- Mounting directly on DIN rail
- Operating current up to 63 A
- Leakage current-free
| IEC category | Type 2 /class II |
| Nominal voltage DCUN | 36 V= |
| Nominal voltage ACUN | 30 V~ |
| Max. continuous operating voltage DCUc | 65 V= |
| Max. continuous operating voltage AC (50/60 Hz) Uc | 45 V~ |
| Max. acceptable fuse or back-up fuse | 63 A gG |
| Voltage protection level (1 kV/μs)Up | ≤ 0,55 kV |
| Protection level at 1 kV/µs (1, 2-PE)Up | ≤ 0,55 kV |
| Response timetA | ≤ 50 ns |
| Nominal discharge current (8/20 µs)In | 20 kA |
Additional Information
| Max. impulse discharge current (8/20 µs)Imax | 40 kA |
| Lightning impulse current (10/350 µs) per poleIimp | 5 (2,5 As) kA |
| Operating temperature rangeTU | -40 - +80 °C |
| Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
| Max. connection torque for terminals | 4,0 Nm |
| Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
| Degree of protection (IEC EN 60529) | IP 20 |
| Mounting on | 35 mm DIN rail (EN 60715) |
| Max. conductor cross section FM | 1,5 mm² |
| Max. switching capacity of remote signal contact | 250 / 2 V/A |