449080_TSF 100-Tr_v02.jpg
A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines.
  • Gasfilled spark gap (TS)
  • AC spark-over voltage : 70 V
  • DC spark-over voltage : 100 V bzw. 500 V
  • DC impulse spark-over voltage (1kV/µs): 650 V
  • Light. imp. current resistance (10/350µs): 100 kA
  • Mounting on 35 mm DIN rail (EN 60715)
  • Test standard DIN EN 62561-3:2018-02
  • Degree of protection according to IEC EN 60529: IP 20
  • EAC certification
IEC category Class H
Nominal DC sparkover voltage at 100 V/sUagN 500 ±20% V=
Nominal AC sparkover voltage (50 Hz)Uaw 350 ±20% V
Typical impulse sparkover voltageUas 950 V
Max. impulse sparkover voltageUas 1300 V
Lightning impulse current (10/350 µs)Iimp 75 kA
Lightning impulse current (10/350 µs) totalItotal 100 kA
Nominal impulse discharge current (10 x 8/20 µs)In 100 kA
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100/1 A/s
Nominal alternating discharge current (50 Hz) 200 / 0,5 A/s
Additional Information
Alternating current critical load (50 Hz) (1x 0.3s)Iwgr 4.000 / 0,25 Aeff/s
Spark-gap extinguishing conditionsVex < 230 V/ < 100 A
Insulation resistance at 10 V, 100 V ≥ 1 GΩ
Self-capacitance at 1 kHz 4 pF
Relative humidity 10%-95% rh
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Mounting on 35 mm DIN rail (EN 60715)
Degree of protection (IEC EN 60529) IP 20
3x lightning impulse current (10/350 µs), long-duration current (CENELEC/BTTF 62-2)Iimp 75kA / 38 As / 1,45 MJ /Ω + 150A / 0,5s /75 As
20x lightning impulse current (10/45 µs) half-wave (DIN 48810) 60kA / 10 As / 0,1 MJ/Ω
Dimension (DIN 43880) 2 TE