487808_HSCS-500-FM.jpg
A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines. For internal or similar applications.
  • With remote signalling contact (FM)
  • High-perfomance short circuit switch
  • High-perfomance short circuit switch
  • High-quality industrial ceramics
  • Rare-gas filled, hermetically sealed
  • Free from radioactive substances
  • High lightning current discharge capacity of 100 kA (10/350 µs) (class H)
  • High reliability, robust
  • Stable performance, long service life
  • Fail-safe characteristic
  • Test standard DIN EN 62561-3:2018-02
IEC category Class H
Nominal DC sparkover voltage at 100 V/sUagN 100 ±20% V=
Nominal AC sparkover voltage (50 Hz)Uaw 70 ±20% V
Typical impulse sparkover voltageUas 650 V
Max. impulse sparkover voltageUas 950 V
Lightning impulse current (10/350 µs)Iimp 75 kA
Lightning impulse current (10/350 µs) totalItotal 100 kA
Nominal impulse discharge current (10 x 8/20 µs)In 100 kA
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100 / 1 A/s
Nominal alternating discharge current (50 Hz) 200 / 0,5 A/s
Additional Information
Spark-gap extinguishing conditionsVex <70V / <20A
Insulation resistance at 10 V, 100 V > 1 GΩ
Short-circuit current ratingISCCR 7,2 kA r.m.s./300 ms kA
Self-capacitance at 1 kHz 6 pF
Test category/climatic category DIN IEC 60068-1 / 40/90/21
Relative humidity 10%...95% rh
Degree of protection IP 20
Operating temperature rangeTU -40 - +80 °C
Terminals M8 bolt/nut (NIROSTA stainless steel)
Dimensions (Ø × L) 25 x 88 mm
3x lightning impulse current (10/350 µs), long-duration current (CENELEC/BTTF 62-2)Iimp 75 kA/ 38 As/ 1,45 MJ / Ω + 150A / 0,5s / 75 As
20x lightning impulse current (10/45 µs) half-wave (DIN 48810) 60kA / 10 As / 0,1 MJ/Ω
Alternating current critical load (50 Hz) (1x 0.3s)Iwgr 4.000 / 0,25 Aeff/s

Related Products