362040_EP-T3_230 SDU.jpg
Two-pole surge arrester for the protection of electronical devices, for the retrofitting of 230 V flush-mounted boxes.
  • Surge voltage protector (class III T3 )
  • Applicable at the LPZ transition point 2-3
  • Test standard: IEC 61643-11 / EN 61643-11
  • Valve arrester SPD (leakage-current free)
  • acoustical indication
  • EAC certification
IEC category Type 3 / class III
Nominal voltage ACUN 230 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Rated load currentIL 16 A
Combined surgeUoc 6 kV
Protection level L-NUp ≤ 1,3 kV
Protection level L/N-PEUp ≤ 1,5 kV
Max. acceptable fuse or back-up fuse 16 A gG
Response time L-N/L,N-PE ≤ 25 / ≤ 100 ns
Nominal discharge current (8/20 µs)In 3 kA
Additional Information
Max. impulse discharge current (8/20 µs)Imax 8 kA
Operating temperature rangeTU -20 - +60 °C
Type of connection 3 lines
Mounting installation in 230V flush sockets
Degree of protection (IEC EN 60529) IP 21