382022_EnerPro 220Tr_20kA_v02.jpg
Two-pole compact SPD with a discharge capacity of 20 kA (8/20 ?s) and disconnection device without interruption of the power supply (red LED).
  • With potential-free remote signalling contact (Pk)
  • SPD Class II+III (T2+T3)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Leakage current-free
  • EAC certification
IEC category Type 2 + 3 / class II + III
Nominal voltage ACUN 230 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 275 V~
Rated load currentIL 16 A
Max. allowed fuse or back-up fuse 16 A gG
Protection level L-NUp ≤ 1,2 kV
Protection level L/N-PEUp ≤ 1,4 kV
Response time L-N/L,N-PE ≤ 25/≤ 50 ns
Nominal discharge current (8/20 µs)In 20 kA
Max. impulse discharge current (8/20 µs)Imax 20 kA
Additional Information
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 2.5mm² solid or 1.5mm² flexible with sleeve
Recommended conductor cross section 1,5 / 2,5 mm²
Max. connection torque for terminals 1,5 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on 35 mm DIN rail (EN 60715)
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section Pk 1,5 mm²