Surge protection for equipment and installations up to 100 A and 150 V.
- Surge Protective Device type 2, class II
- High performance arrester for 150 V operating voltage
- Function control indication via LED
- Signalling contact (break contact) with pluggable terminal (Pk)
- EAC certification
| IEC category | Type 2 + 3 / class II + III |
| Nominal voltage DCUN | 150 V= |
| Nominal voltage ACUN | 120 V~ |
| Max. continuous operating voltage AC (50/60 Hz) Uc | 170 V~ |
| Protection levelUp | ≤ 1,0 kV |
| Lightning impulse current (10/350 µs)Iimp | 8 kA |
| Max. impulse discharge current (8/20 µs)Imax | 40 kA |
| Max. allowed fuse or back-up fuse | 125 A gG |
| Response timetA | ≤ 25 ns |
| Max. conductor cross section | 50 mm² single wire / 35 mm² stranded / 25 mm² fine-stranded with sleeve |
Additional Information
| Max. connection torque for terminals | 1,5 Nm |
| Operating temperature rangeTU | -40 - +80 °C |
| Degree of protection (IEC EN 60529) | IP 20 |
| Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
| Mounting on | 35 mm DIN rail (EN 60715) |
| Max. conductor cross section Pk | 1,5 mm² |
| Max. current carrying capacity PK | 250 V/2 A |
| Power supply system | 1 phase TN systems |