Compact and leakage-current free 2-pole surge arrester with looped-in wiring, e.g. for the protection of TN systems by applying only one module in the sub-distribution board.
- Surge Protective Device type 2, class II
- Test standard: IEC 61643-11 / EN 61643-11
- Monitoring of conductor and arrester via LED
- Looped-in wiring (in series) max. nominal current 16A
- Mounting on 35 mm DIN rail (EN 60715)
- Degree of protection according to IEC EN 60529: IP 20
- EAC certification
| IEC category | Type 2 /class II |
| Nominal voltage ACUN | 230 V~ |
| Max. continuous operating voltage AC (50/60 Hz) Uc | 275 V~ |
| Max. operating currentIL | 16 A |
| Protection level at 5 kAUp | ≤ 1,0 kV |
| Protection level at In (8/20 µs)Up | ≤ 1,4 kV |
| Response timetA | < 50 ns |
| Nominal discharge current (8/20 µs)In | 15 kA |
| Max. impulse discharge current (8/20 µs)Imax | 40 kA |
| Max. allowed fuse or back-up fuse | 16 A gG |
Additional Information
| Operating temperature rangeTU | -40 - +80 °C |
| Max. conductor cross section | stranded 35/fine stranded 25 mm² |
| Recommended conductor cross section | 16 mm² |
| Max. connection torque for terminals | 4,0 Nm |
| Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
| Degree of protection (IEC EN 60529) | IP 20 |
| Mounting on | 35 mm DIN rail (EN 60715) |
| Power supply system | 1 phase TN systems |