A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines. For internal or similar applications.
- Isolating spark gap in holder
- Gasfilled spark gap (TS)
- High-quality industrial ceramics
- Rare-gas filled, hermetically sealed
- Free from radioactive substances
- High lightning current discharge capacity of 100 kA (10/350 µs) (class H)
- High reliability, robust
- Stable performance, long service life
- Fail-safe characteristic
- Test standard DIN EN 62561-3:2018-02
| IEC category | Class H |
| Nominal DC sparkover voltage at 100 V/sUagN | 100 ±20% V= |
| Nominal AC sparkover voltage (50 Hz)Uaw | 70 ±20% V |
| Typical impulse sparkover voltageUas | 650 V |
| Max. impulse sparkover voltageUas | 950 V |
| Lightning impulse current (10/350 µs)Iimp | 75 kA |
| Lightning impulse current (10/350 µs) totalItotal | 100 kA |
| Nominal impulse discharge current (10 x 8/20 µs)In | 100 kA |
| 5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn | 100/1 A/s |
| Nominal alternating discharge current (50 Hz) | 200/0,5 A/s |
Additional Information
| Spark-gap extinguishing conditionsVex | <70 V / <20 A |
| Insulation resistance at 10 V, 100 V | < 1 GΩ |
| Self-capacitance at 1 kHz | 6 pF |
| Test category/climatic category | DIN IEC 60068-1 / 40/90/21 |
| Relative humidity | 10%...95% rh |
| Degree of protection (IEC EN 60529) | IP 67 |
| Operating temperature rangeTU | -40 - +80 °C |
| Terminals | M8 bolt/nut (NIROSTA stainless steel) |
| Dimensions (L x W x H) |