Two-pole surge arrester for the protection of electronical devices, for the retrofitting of 230 V flush-mounted boxes.
- Surge voltage protector (class III T3 )
- Applicable at the LPZ transition point 2-3
- Test standard: IEC 61643-11 / EN 61643-11
- Valve arrester SPD (leakage-current free)
- acoustical indication
- EAC certification
| IEC category | Type 3 / class III |
| Nominal voltage ACUN | 230 V~ |
| Max. continuous operating voltage AC (50/60 Hz) Uc | 255 V~ |
| Rated load currentIL | 16 A |
| Combined surgeUoc | 6 kV |
| Protection level L-NUp | ≤ 1,3 kV |
| Protection level L/N-PEUp | ≤ 1,5 kV |
| Max. acceptable fuse or back-up fuse | 16 A gG |
| Response time L-N/L,N-PE | ≤ 25 / ≤ 100 ns |
| Nominal discharge current (8/20 µs)In | 3 kA |
Additional Information
| Max. impulse discharge current (8/20 µs)Imax | 8 kA |
| Operating temperature rangeTU | -20 - +60 °C |
| Type of connection | 3 lines |
| Mounting | installation in 230V flush sockets |
| Degree of protection (IEC EN 60529) | IP 21 |